APC HIGH PERFORMANCE BATTERY MODULE
High-Performance Battery Module for 400V Symmetra PX 48/96/160KW & 208V Symmetra PX 100KW
Main documents
Documents
Product Datasheet
action_download_stroke
Environmental Disclosure
action_download_stroke
See all documents
+ Lifecycle Services
Sort by:
Start-Up Service 5X8 for (1) External Battery Frame for Symmetra PX 160 kW
WSTRTUP-PX-63
Specifications
Lead time | Usually in Stock |
---|
Battery Type | VRLA |
---|---|
Provided Equipment | Installation guide |
Battery Placement | Internal Battery |
---|---|
Battery blocks per string | 4 |
Battery Voltage | 384 V |
battery power in VAh | 3456 VAh |
Height | 6.26 in (15.9 cm) |
---|---|
Width | 16.85 in (42.8 cm) |
Depth | 27.56 in (70 cm) |
Net Weight | 221.45 lb(US) (100.45 kg) |
Standards | UL 1778 |
---|---|
Product Certifications | CE Eurobat General Purpose |
Ambient Air Temperature for Operation | 32…104 °F (0…40 °C) |
---|---|
Operating altitude | 0…3333 ft |
Relative Humidity | 0…95 % |
Ambient Air Temperature for Storage | 5…104 °F (-15…40 °C) |
Storage altitude | 0…50000 ft (0.0000000000…15240.0000000000 m) |
Storage Relative Humidity | 0…95 % |
GTIN | 3606489862886 |
---|
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Height | 7.09 in (18 cm) |
Package 1 Width | 31.89 in (81 cm) |
Package 1 Length | 23.62 in (60 cm) |
Package 1 Weight | 236.8 lb(US) (107.4 kg) |
Warranty | 1 year (parts only) |
---|
Environmental Data
Schneider Electric aims to achieve Net Zero status by 2050 through supply chain partnerships, lower impact materials, and circularity via our ongoing “Use Better, Use Longer, Use Again” campaign to extend product lifetimes and recyclability.
Environmental Data explained
How we assess product sustainability
Carbon footprint (kg CO2 eq, Total Life cycle)
information_stroke
1
Environmental Disclosure
information_stroke
Product Environmental Profile
Use Better
Packaging made with recycled cardboard
information_stroke
Yes
Packaging without single use plastic
information_stroke
No
EU RoHS Directive
information_stroke
Pro-active compliance (Product out of EU RoHS legal scope)
SCIP Number
information_stroke
5ac12844-46eb-471b-94f1-318e06a714a6
REACh Regulation
information_stroke
REACh Declaration
California proposition 65
information_stroke
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Use Again
Take-back
information_stroke
Yes
Documents
Filter by
8 Results
Document Category
Language
English
Symmetra PX 48 kW, 96 kW, and 160 kW EU Declaration of Conformity (V6)
PDF (231.9 KB) | Nov 28 2024 | Declaration of conformity – EU/CE
SYBT9-B4 REACh Declaration
PDF (195.3 KB) | Jan 03 2025 | Declaration of conformity – REACh Declaration
Symmetra PX 208 V Certificate of Origin (V3)
PDF (71.3 KB) | Sep 05 2024 | Certificate of Origin
Symmetra PX 48, Symmetra PX 96-160 kW 400 V Certificate of Origin (V5)
PDF (71.8 KB) | Sep 05 2024 | Certificate of Origin
Symmetra PX 48/96/160 kW UCKA Declaration of Conformity (V1)
PDF (311.9 KB) | Oct 20 2023 | Declaration of conformity – EU/CE
SYBT9-B4 EU RoHS Declaration
PDF (195.3 KB) | Jan 03 2025 | Declaration of conformity – EU RoHS Declaration
Symmetra PX 48-160 kW Cmim Declaration of Conformity (V0)
PDF (123.8 KB) | Jul 14 2019 | Certificate
Battery Modules, ENV Disclosure, PEP, Schneider Electric (V1)
PDF (325.3 KB) | Jan 08 2016 | Environmental Disclosure – Product Environmental Profile